Troubleshooting Steps
To resolve this issue, follow the steps below:
Disconnect the Olarm MAX, including the super capacitor (allow the Olarm MAX to turn off)
On the DSC NEO panel, go to location 380 and disable Comms.
Go to location 382 and disable Alternative Comms.
Restart the DSC NEO panel.
After the panel restarts, go back to:
Location 380 and enable Comms
Location 382 and enable Alternative Comms
Reconnect the Olarm MAX, including the super capacitor.
If signals are not being received by the control room:
Account code setup: Ensure that account codes for the relevant partitions are programmed as per the control room's configuration in the Olarm Command Centre.
Navigate to:
Location 310 (System Account Codes)
Program account codes for each active partition.
If you're seeing an FTC trouble condition on receiver 4:
Phone number configuration: Set receiver 4’s phone number to the default fail-safe value.
Navigate to:
Location 301 (Phone Number Programming)
Receiver 004: Enter
FFFFFFFFFFFFFFFF
FFFFFFFFFFFFFFFF
If arming fails but other commands work:
Quick arm setting: Make sure the quick arm function is enabled in programming.
Navigate to:
Location 015
Enable Option 4
Always reboot the alarm panel after making programming changes to ensure all settings apply correctly.