Programming checks: Ensure the following locations are correctly configured:
Location 300 (Communication Path)
Receiver 1: Set to Alt Comm Auto
Receiver 2: Set to Alt Comm Rec 1
Location 380 (Communication Options)
Com Opt 1 must be enabled
Location 382 (Communication Option 3)
Enable Alternate Comm
Location 383 (Communication Option 4)
Enable FTC Comms
If signals are not being received by the control room:
Account code setup: Ensure that account codes for the relevant partitions are programmed as per the control room's configuration in the Olarm Command Centre.
Navigate to:
Location 310 (System Account Codes)
Program account codes for each active partition.
If you're seeing an FTC trouble condition on receiver 4:
Phone number configuration: Set receiver 4’s phone number to the default fail-safe value.
Navigate to:
Location 301 (Phone Number Programming)
Receiver 004: Enter
FFFFFFFFFFFFFFFF
FFFFFFFFFFFFFFFF
If arming fails but other commands work:
Quick arm setting: Make sure the quick arm function is enabled in programming.
Navigate to:
Location 015
Enable Option 4
Always reboot the alarm panel after making programming changes to ensure all settings apply correctly.