Ensure that the DSC PowerSeries alarm panel is running firmware version V1.5.1 or higher.
If you have more than one keypad connected to the system:
Keypad configuration: Set at least one keypad to Global and Slot 1. The remaining keypads can then be configured according to their respective partition and slot.
To configure the keypad:
Press [*] [8] [Installer’s Code] – Enter Installer Programming
Press [0] [0] [0] – Enter Keypad Assignment Section
Press [0] [1] – Enter Partition and Slot Assignment
If the Evolution Kit stops responding after installation:
Wireless receiver conflict: Add a PC5320 wireless receiver module to resolve the issue.
Alternatively, disconnect the existing receiver from the alarm panel.
If arming works but disarming fails:
Master code mismatch: Ensure that the Master Keypad Code is entered correctly in the Olarm APP.
If you’re unable to arm or disarm at all:
Quick arm function: Verify that Quick Arm is enabled in the panel’s programming.
Navigate to:
Location 015
Enable Option 4